ZP7 Series addressable MCP, red flush mount with EN54 marking
  • Modern stylish design
  • Resettable or frangible operating elements supported
  • Single maintenance and test tool
  • Plug-in loop connection for easy installation
View all

At a glance

General

The ZP785-3 is an addressable call point of stylish design, providing a manual means of initiating a fire alarm on ZP2 & ZP3 addressable systems. Certified to EN54:11, the ZP785-3 is suitable for installations meeting the recommendations of many local codes (e.g. BS 5839:1).
The unit is operated either by pressing a resettable element or by breaking a frangible glass with finger pressure. Glass elements have clear vinyl coatings on the front surface to prevent operator injury and to inhibit the release of loose fragments as the glass is broken. Both operating elements are easily interchangeable.
Rated at IP24 the ZP785-3 moulding is constructed of ABS plastic and intended for indoor applications. A red LED indicator is prominently positioned on the front of the unit. This LED illuminates when the device is activated.

Installation

Installed as part of a Ziton addressable system, up to 127 devices (call points, detectors and interface units) may be connected to each of the control panel loops. All loop devices incorporate switch settings enabling them to be assigned a unique address which is polled by the panel every two seconds.
ZP785-3 call points are designed for semi recessed fixing, using a standard single gang socket box, or can be surface mounted by means of a DMN787 matching plastic back box. Push in terminals enable the device to be plugged directly into the loop, making replacement simple and reducing internal cable ends to a minimum.
System testing, glass replacement and device reset are carried out by using a special maintenance tool. This tool enables part of the front moulding including the glass to be lowered, allowing the device to operate.

Poly-carbonate front cover

For locations where malicious operation or accidental impact from flying objects may occur (for example sports halls), operation can be restricted by the addition of a clear, polycarbonate, front cover (DMN782), which can be further protected by a cover seal (DMN798).

Details

  • Modern stylish design
  • Resettable or frangible operating elements supported
  • Single maintenance and test tool
  • Plug-in loop connection for easy installation

Technical specifications

General
Status indication
Red LED
Compatibility
All ZP7 addressable systems
Connectivity
2 wire loop
Addressing method
DIP Switches
Electrical
Power supply type
Loop powered
Operating voltage
19.5 to 20.5 V
Communication voltage
19.5 to 20.5 V
Current consumption
400 µA (quiescent)
450 µA (alarm)
Cable specification
0.5 to 2.5 mm²
No. of cable cores
2
Terminals
4
Detection
Detection principle
Micro switch
Monitoring
Activated
Standby
Installation height
Determined by local regulation
Physical
Physical dimensions
93 x 89 x 28 mm (H x W x D)
Net weight
130 g
Colour
Red (RAL 3001)
Mounting type
Recessed mount
Wall mount
Cable entries
1
Material (body)
PC / ABS
Functional marking
House on Fire
Fixing centres
60 mm
Environmental
Vandal proof
No
Operating temperature
-10 to +55°C
Storage temperature
-10 to +55°C
Relative humidity
93± 3% noncondensing
Environment
Indoor
IP rating
IP24D
Regulatory
Compliancy
CE
REACH
RoHS 3
WEEE
Certification
CPR
Standards
EN54-11
EEC89/336

Compatible products

Category Reference Description
Detection device DM715 EN54 Universal MCP glass, without branding
Detection device DMN787 Surface mounting box with earth connector, red
Detection device DMN800 Resettable element for Manual Call Point