AirSense Stratos HSSD2 High Sensitivity Smoke Detector - Minimum display version
- High sensitivity provided by laser based forward light scatter for reliable early warning
- Combined sampling pipe up to 200m in length (still air)
- Unique ClassiFire® Perceptive Artificial Intelligence system that dynamically adjusts the detector’s operating parameters, allowing for day to day changes in the protected environment and dust separation system contamination
- Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3 Laser Dust Discrimination and elimination system
- RS485 communications built in as standard for networking and remote communications
At a glance
Description
AirSense Stratos HSSD2 is designed to provide very high sensitivity smoke detection, ensuring the very earliest warning of incipient fire with minimum rate of nuisance alarms.
ClassiFire Perceptive Artificial Intelligence ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup. This means the product will configure itself to provide high sensitivity in a computer room or reduced sensitivity in a smoky area.
Upgradable volt-free Fire and Fault relay outputs are available for remote monitoring by local fire detection or BMS systems.
ClassiFire Perceptive Artificial Intelligence ensures that the detector operates at optimum sensitivity for the protected environment, without the need for complex setup. This means the product will configure itself to provide high sensitivity in a computer room or reduced sensitivity in a smoky area.
Upgradable volt-free Fire and Fault relay outputs are available for remote monitoring by local fire detection or BMS systems.
Typical Applications
• Data storage units
• Prison cells
• Plant rooms
• Air conditioning units
• Equipment racks
• Computer rooms
• Air duct protection
• Heritage property protection
• Critical equipment
• Anti-smoking enforcement
• Motor rooms
• Prison cells
• Plant rooms
• Air conditioning units
• Equipment racks
• Computer rooms
• Air duct protection
• Heritage property protection
• Critical equipment
• Anti-smoking enforcement
• Motor rooms
Options Available
• Addressable Protocol Interface Cards APIC™ available various protocols
• Command Module available for central monitoring and display
• SenseNet compatible - up to 127 detectors per loop
• Remote Display units available
• Suitable for MatrixScan, a patented software system which provides virtual addressable location detection - e.g. 10 physical detectors would provide up to 45 unique addressable locations.
• Command Module available for central monitoring and display
• SenseNet compatible - up to 127 detectors per loop
• Remote Display units available
• Suitable for MatrixScan, a patented software system which provides virtual addressable location detection - e.g. 10 physical detectors would provide up to 45 unique addressable locations.
Details
- High sensitivity provided by laser based forward light scatter for reliable early warning
- Combined sampling pipe up to 200m in length (still air)
- Unique ClassiFire® Perceptive Artificial Intelligence system that dynamically adjusts the detector’s operating parameters, allowing for day to day changes in the protected environment and dust separation system contamination
- Unwanted alarms from dust are avoided using patented Dual Technology LDD 3D3 Laser Dust Discrimination and elimination system
- RS485 communications built in as standard for networking and remote communications
- Large area aspirating smoke detector, up to 2000m2 coverage
- CPR, VdS & UL approved
Technical specifications
| General | ||
|---|---|---|
| User interface |
LED
|
|
| Electrical | ||
|---|---|---|
| Operating voltage |
21.6 to 26.4 VDC
|
|
| Current consumption |
450 mA at fan speed 8
|
|
| Detection | ||
|---|---|---|
| Detection principle |
Laser light scattering mass detection and particle evaluation
|
|
| Range |
0.0015% to 25% (%Obs/m)
|
|
| Particle sensitivity range |
0.003μ to 10μ
|
|
| Alarm levels | 4 (Aux, Pre-alarm, Alarm and Alarm 2) | |
| Sampling pipe | ||
|---|---|---|
| Length |
100 m maximum single run (50 m in moving air), 200 m Combined maximum
|
|
| Inlet quantity |
4
|
|
| Inlet size |
27 mm OD
|
|
| Exhaust |
1 (optional)
|
|
| Input | ||
|---|---|---|
| Input quantity |
3, Progammable
|
|
| Output | ||
|---|---|---|
| Output quantity |
5, Pre-Alarm, Alarm, Alarm2, Aux Alarm (n/o) and Fault (n/c)
|
|
| Output type and rating |
500 mA @ 30 V
|
|
| Physical | ||
|---|---|---|
| Physical dimensions |
427 x 372 x 95 mm (W x H x D)
|
|
| Net weight |
5.2 kg
|
|
| Colour |
Cream
|
|
| Mounting type |
Wall mount
|
|
| Cable entries |
6 x M20
|
|
| Material (body) |
Sheet steel
|
|
| Environmental | ||
|---|---|---|
| Operating temperature |
-10 to +60°C (EN54-20)
|
|
| Relative humidity |
0 to 90% noncondensing
|
|
| Environment |
Indoor
|
|
| IP rating |
IP40
|
|
| Regulatory | ||
|---|---|---|
| Certification |
EN54-20
UL
|
|
| Sampling pipework | ||
|---|---|---|
| Holes | up to 100 holes | |
Downloads
All downloadsDatasheet
Technical documentation
CPD / CPR
CPD / CPR
CPR_2831-CPR-F1187_Stratos HSSD2 MD
CPD / CPR
UKCA-CPR_0832-UKCA-CPR-F1250_Stratos HSSD2 MD
Certificates
DoP
KGS F&S - DoP_360-3514-0399_HSSD2 Minimum Display
DoC
KGS F&S - DoC_10-3514-356-0199_HSSD2
Non EU certificate
FM - VMC_3014717_Stratos HSSD2
Other EU certificate
Other EU certificate
VMC_G203024_Stratos HSSD2
Other EU certificate
VMC_MPL 049 C2_Stratos HSSD2 MD
Other EU certificate
VMC_1199d-(cl-1)_ASD
If available, the downloads of the Certificates, Software & Firmware and Media are displayed in their default language.