Hoppa till huvudinnehåll

AACUSP

Konventionell kontrollenhet till analog värmedetektorkabel, med display
  • UL521 and CE approval, UL/ULC listed
  • Up to 500m of sensor cable per zone
  • Separate pre-alarm and alarm signals
  • Easy programmable interface
  • Enclosure temperature alarm
Se alla

På kartan

General

The AACUSP is a self programmable, Analogue Liner Heat Detection (LHD) cable control unit. It provides monitoring for any of the Alarmline II range of LHD sensor cable, configuration of alarm and pre-alarm temperatures as well as enabling simple interface to a main fire alarm or BMS system.

Interface & Programming

The AACULP provides LED indications as well as an LCD. Internal pushbuttons allow configuration without the need for a PC.

Pre-Alarm and Alarm thresholds can be set through simple menu options with no need for any graphs or nomograms. Initial set-up is done by measuring and entering the calibration resistance of the sensor cable removing the need to know the sensor cable length.

Volt free changeover contacts are provided inside the control unit for Pre-Alarm and Alarm signaling to a main fire alarm control panel or BMS system. A failsafe opto-isolated phototransistor fault output is also provided.

No user controls are provided on the control unit. An isolated input is provided enabling remote reset functionality.

Operation

As well as monitoring the LHD sensor cable for changes in temperature, the control unit also monitors for open and short circuit faults along the cable ensuring notification if the cable becomes damaged.It is fitted with its own internal temperature monitor and should the temperature within the controller enclosure reach 100°C (212°F), an alarm will be signaled.

Each control unit may have up to 500m (1640ft) of LHD sensor cable connected to it, acting as a single detection zone. When the LHD sensor cable and the control unit are installed in different areas, a suitable interposing cable can be used to make the electrical connection between them.

Detaljer

  • UL521 and CE approval, UL/ULC listed
  • Up to 500m of sensor cable per zone
  • Separate pre-alarm and alarm signals
  • Easy programmable interface
  • Enclosure temperature alarm
  • IP66 rated enclosure
  • No nomograms or charts required

Tekniska specifikationer

Physical
Colour
Ljusgrå
Mounting type
Forsænket montering
Material (body)
Polycarbonat
Environmental
Environment
Indendør
Udendørs
Regulatory
Certification
CE
UL

Nedladdningar

All downloads

Datablad

Certificaten

Om tillgängligt visas nedladdningarna av certifikat, programvara och fast programvara och media på deras standardspråk.